EDS-2008-ELP
EDS-2008-ELP – Switch Ethernet-Managed-8 cổng 10/100Baset(x)
Ethernet Interface
-
10/100BaseT(X) Ports (RJ45 connector)
- 8
Full/Half duplex mode
Auto MDI/MDI-X connection
Auto negotiation speed
- 8
-
Standards
- IEEE 802.3 for 10BaseT
IEEE 802.1p for Class of Service
IEEE 802.3u for 100BaseT(X)
IEEE 802.3x for flow control
- IEEE 802.3 for 10BaseT
-
Optical Fiber
-
Optical Fiber
100BaseFX Multi-Mode Single-Mode Fiber Cable Type OM1 50/125 µm G.652 800 MHz x km Typical Distance 4 km 5 km 40 km Wavelength Typical (nm) 1300 1310 TX Range (nm) 1260 to 1360 1280 to 1340 RX Range (nm) 1100 to 1600 1100 to 1600 Optical Power TX Range (dBm) -10 to -20 0 to -5 RX Range (dBm) -3 to -32 -3 to -34 Link Budget (dB) 12 29 Dispersion Penalty (dB) 3 1
Switch Properties
-
Processing Type
- Store and Forward
-
MAC Table Size
- 8 K
-
Packet Buffer Size
- 4 Mbits
DIP Switch Configuration
-
Ethernet Interface
- Quality of Service (QoS), Broadcast Storm Protection (BSP)
Power Parameters
-
Connection
- 1 removable 3-contact terminal block(s)
-
Input Current
- 0.067 A @ 24 VDC
-
Input Voltage
- 12/24/48 VDC
-
Operating Voltage
- 9.6 to 60 VDC
-
Overload Current Protection
- Supported
-
Reverse Polarity Protection
- Supported
Physical Characteristics
-
Dimensions
- 36 x 81 x 65 mm (1.4 x 3.19 x 2.56 in)
-
Installation
- DIN-rail mounting, Wall mounting (with optional kit)
-
Housing
- Plastic
-
Weight
- 90 g (0.2 lb)
Environmental Limits
-
Ambient Relative Humidity
- 5 to 95% (non-condensing)
-
Operating Temperature
- -10 to 60°C (14 to 140°F)
-
Storage Temperature (package included)
- -40 to 85°C (-40 to 185°F)
Standards and Certifications
-
Safety
- UL 61010-2-201, EN 62368-1 (LVD)
-
EMC
- EN 55032/35
-
EMI
- CISPR 22, 32, FCC Part 15B Class A
-
EMS
- IEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV
IEC 61000-4-3 RS: 80 MHz to 1 GHz: 20 V/m
IEC 61000-4-4 EFT: Power: 2 kV; Signal: 2 kV
IEC 61000-4-5 Surge: Power: 2 kV; Signal: 2 kV
IEC 61000-4-6 CS: 10 V
IEC 61000-4-8 PFMF
- IEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV
-
Shock
- IEC 60068-2-27
-
Vibration
- IEC 60068-2-6
-
Freefall
- IEC 60068-2-32
MTBF
-
Time
- 3,472,660 hrs
-
Standards
- Telcordia (Bellcore), GB