NDR-120-48
NDR-120-48
NAME | TYPE | VERSION | RELEASE DATE |
---|---|---|---|
QIG for NDR Power Supply Series
258.4 KB |
QIG | v1.1 | Jun 07, 2021 |
Datasheet for NDR Power Supply Series
1.2 MB |
Datasheet | v1.1 | Apr 07, 2020 |
Output Power Parameters
-
Wattage
- 120 W
-
Voltage
- 48 VDC
-
Current Rating
- 0 to 2.5 A
-
Ripple and Noise
- 150 mVp-p
-
Voltage Adjustment Range
- 48 to 55 VDC
-
Setup/Rise Time at Full Load
- 2500 ms, 60 ms at 115 VAC
1200 ms, 60 ms at 230 VAC
- 2500 ms, 60 ms at 115 VAC
-
Typical Hold Up Time at Full Load
- 10 ms at 115 VAC
16 ms at 230 VAC
- 10 ms at 115 VAC
Input Power Parameters
-
Typical Efficiency
- 89%
-
Typical Current
- 1.3 A @ 230 VAC, 2.25 A @ 115 VAC
-
Voltage Range
- 90 to 264 VAC (47 to 63 Hz)
127 to 370 VDC
- 90 to 264 VAC (47 to 63 Hz)
-
Inrush Current (cold start)
- 35 A @ 230 VAC, 20 A @ 115 VAC
Overload Protection
-
Rated Output Power
- 105 to 160%
-
Protection Type
- Constant current limiting, recovers automatically after fault condition is removed
Overvoltage Protection
-
Over-Voltage Range
- 56 to 65 V
-
Protection Type
- Shut down operating voltage, repower on to recover
Physical Characteristics
-
Housing
- Metal
-
Dimensions
- 123.75 x 125.20 x 40 mm (4.87 x 4.93 x 1.57 in)
-
Weight
- 500 g (1.10 lb)
Environmental Limits
-
Operating Temperature
- -20 to 70°C (-4 to 158°F)
-
Storage Temperature
- -40 to 85°C (-40 to 185°F)
-
Ambient Relative Humidity
- 20 to 95% (non-condensing)
-
Max. Operating Temperature at Full Load
- 45°C (113°F)
Standards and Certifications
-
Safety
- UL 508, EN 62368-1, IEC 62368-1
-
EMC
- EN 55032/24, EN 61000-3-2 Class A, EN 61000-3-3
-
EMS
- IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV
IEC 61000-4-3 RS: 80 MHz to 1 GHz: 3 V/m
IEC 61000-4-4 EFT: Power: 2 kV
IEC 61000-4-5 Surge: Power: 2 kV
IEC 61000-4-6 CS: 10 V
IEC 61000-4-8 PFMF
IEC 61000-4-11 DIPs
- IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV
MTBF
-
Standards
- MIL-HDBK-217F
-
Time
- 453,334 hrs