FB6308B2 Digital Output with Shutdown Input
Item Number: FB6308B2
- 8-channel
- Outputs with plug-in Ex e terminals
- Installation in suitable enclosures in Zone 1
- Module can be exchanged under voltage (hot swap)
- Line fault detection (LFD)
- Positive or negative logic selectable
- Simulation mode for service operations (forcing)
- Permanently self-monitoring
- Output with watchdog
- Output with bus-independent safety shutdown input
- Output with bus-independent safety shutdown
LED indication LED green: supply
LED red: line fault , red flashing: communication error
Damaging gas | EN 60068-2-42:2003 |
Storage temperature | -25 … 85 В°C (-13 … 185 В°F) |
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
Ambient temperature | -20 … 60 В°C (-4 … 140 В°F) |
Vibration resistance |
frequency range 10 … 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration В± 0.075 mm/1 g; 10 cycles frequency range 5 … 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration В± 1 mm/0.7 g; 90 minutes at each resonance |
Coding | optional mechanical coding via front socket |
Power dissipation | 2.35 W |
Dimensions | 57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch) |
Rated voltage | 12 V DC , only in connection with the power supplies FB92** |
Occupied slots | 2 |
Shock resistance | EN 60068-2-27:2009 |
Relative humidity | EN 60068-2-78:2001 |
Interface | manufacturer-specific bus to standard com unit |
Power consumption | 2.35 W |
Open loop voltage | 20 V |
Response time | 20 ms (depending on bus cycle time) |
Connection | Ex e spring terminal with protective cover |
Connection | channel I: 1+, 2-; channel II: 3+, 4-; channel III: 5+, 6-; channel IV: 7+, 8-; channel V: 9+, 10-; channel VI: 11+, 12-; channel VII: 13+, 14-; channel VIII: 15+, 16- |
Line fault detection | can be switched on/off for each channel via configuration tool |
Connection | backplane bus |
System information | The module has to be mounted in appropriate backplanes (FB92**) in Zone 1, 2, or outside hazardous areas. Observe the corresponding EC-type examination certificate. |
INMETRO | Brazil: TГњV 14.1599X |
Number of channels | 8 |
Electromagnetic compatibility | NE 21:2007 |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
Vibration resistance | EN 60068-2-6:2008 |
EU-Type Examination Certificate | BVS 11 ATEX E 093 X |
Relative humidity |
95 % non-condensing |
Degree of protection | IP20 (module) , a separate housing is required acc. to the system description |
Environmental test | EN 60068-2-14:2009 |
Current limit | 8 mA |
Connection | backplane bus |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 |
ATEX approval | BVS 11 ATEX E 093X |
Degree of protection | IEC 60529:2000 |
Mass | approx. 750 g |
Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication |