LB8109H0906
Pepperl+Fuchs LB8109H0906 Unicom Com Unit for PROFIBUS DP/DP-V1
Rated voltage5 V DC , only in connection with the power supplies LB9***
Vibration resistance | frequency range 10 … 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration В± 0.075 mm/1 g; 10 cycles frequency range 5 … 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration В± 1 mm/0.7 g; 90 minutes at each resonance |
Certificate | PF 08 CERT 1234 X |
Storage temperature | -25 … 85 В°C (-13 … 185 В°F) |
Electromagnetic compatibility |
NE 21 |
Connection | backplane bus |
Power dissipation | 1.8 W |
Cyclic process data | 240 bytes input and (simultaneously) 240 bytes output |
Relative humidity | EN 60068-2-56 |
HART communication | via PROFIBUS or service bus |
PROFIBUS address | 0 … 126 (factory standard setting: 126) |
Degree of protection | IEC 60529 |
System information | The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2, Zone 22 or Div. 2) the module must be installed in an appropriate enclosure. |
Number of repeaters between Master and Slave | max. 3 |
UL approval | E106378 |
Number of stations per bus line | max. 125 (PROFIBUS), max. 119 (service bus) |
Relative humidity | 95 % non-condensing |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 |
ATEX approval | PF 08 CERT 1234 X |
Addressing | via configuration software |
Vibration resistance | EN 60068-2-6 |
Redundancy | via backplane |
Damaging gas | EN 60068-2-42 |
Connection | via backplane |
Degree of protection | IP20 (module) , mounted on backplane |
Connection | backplane bus |
Shock resistance | EN 60068-2-27 |
Bus length |
max. 1000 m (FOL, 1.5 MBaud), max. 1000 m (copper cable, 187.5 kBd), max. 200 m (copper cable, 1.5 MBd) |
Dimensions | 32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch) |
Supported I/O modules | all LB remote I/O modules |
Configuration (240 bytes I/O) | Standard: 80 analog, 184 digital Universal 2I2O: 48 analog, 184 digital Universal 4I4O: 60 analog, 120 digital |
Mass | approx. 120 g |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
Number of stations per bus segment | max. 31 (RS-485 standard) |
Power consumption | 1.8 W |
EAC approval | Russia: RU C-IT.MIII06.B.00129 |
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
LED indication | LED P: (power supply): On = operating, fast flash = cold start, slow flash = HCIR loading active LED 1: (collective alarm): On = internal fault, flashing = no PROFIBUS connection LED 2: (status fieldbus): flashing = PROFIBUS receive channel active LED 3: (status service bus): flashing = service bus receive channel active LED 4: (operating mode): flashing 1 (1:1 ratio) = active, normal operation; flashing 2 (7:1 ratio) = active, simulation LED 5: (status fieldbus): flashing = PROFIBUS response channel active LED 6: (status service bus): flashing = service bus response channel active |
IECEx approval | BVS 09.0037X |
Ambient temperature | -20 … 60 В°C (-4 … 140 В°F) |
Fieldbus standard | IEC 61158-2 |
Fieldbus type | PROFIBUS DP/DP-V1 |
Environmental test | EN 60068-2-14 |
GSE file | CGV61710.gsd/gse |
Xem thêm các sản phẩm khác tại đây https://dailydiencongnghiep.com/san-pham/