M-LB-4.150TNS.D
Pepperl+Fuchs M-LB-4.150TNS.D Surge Protection Barrier
Voltage protection level | max. 0.7 kV max. 0.55 kV at 5 kA |
Core cross-section | – min. 1.5 mm2 solid/flexible – max. 35 mm2 stranded/25 mm2 flexible – max. 1.5 mm2 solid/flexible (for remote signalling contact) |
Temporary over-voltage | 175 V / 5 s (TOV withstand) |
Vibration resistance | EN 60068-2 |
Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 |
Relative humidity | 5 … 95 % |
Network configuration | TN-S |
Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A; 24 V/0.5 A |
Reaction time | max. 25 ns |
Degree of protection | IEC 60529 |
Mass | approx. 480 g |
Number of protected supply lines | 4 |
Max. surge current (8/20 µs) | 40 kA |
Maximum continuous operating voltage | 150 V AC, 50 … 60 Hz |
Dimensions | 72 x 90 x 73 mm (2.8 x 3.6 x 2.9 inch) (4 TE acc. to DIN 43880) |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Nominal discharge current (8/20 µs) | 15 kA |
Degree of protection | IP20 |
Shock resistance | EN 60068-2 |
Short-circuit-proof | 50 kA eff |
Connection | terminals 11, 12, 14 |
Output | volt-free change-over contact |
Nominal voltage | 120 V AC, 50 … 60 Hz 240 V AC, 50 … 60 Hz |
Display elements | status display operating state (green) fault indication (red) |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Suitable components | protection module M-LB-1.150.M |
Ambient temperature | -40 … 80 В°C (-40 … 176 В°F) |
Xem thêm các sản phẩm khác tại đây https://dailydiencongnghiep.com/san-pham/