PN7070
Pressure sensor with display PN7070
Product characteristics |
|||||||||
---|---|---|---|---|---|---|---|---|---|
Output signal | switching signal; IO-Link; (configurable) | ||||||||
Measuring range |
|
||||||||
Process connection | threaded connection G 1/4 internal thread | ||||||||
Application PN7070 | |||||||||
Special feature | Gold-plated contacts | ||||||||
Measuring element | metallic thin film cell | ||||||||
Application | for industrial applications | ||||||||
Media | liquids and gases | ||||||||
Medium temperature [°C] | -25…80 | ||||||||
Min. bursting pressure |
|
||||||||
Pressure rating |
|
||||||||
Vacuum resistance [mbar] | -1000 | ||||||||
Type of pressure | relative pressure | ||||||||
Electrical data | |||||||||
Operating voltage [V] | 18…30 DC; (according to EN 50178 SELV/PELV) | ||||||||
Current consumption [mA] | < 35 | ||||||||
Min. insulation resistance [MΩ] | 100; (500 V DC) | ||||||||
Protection class | III | ||||||||
Reverse polarity protection | yes | ||||||||
Power-on delay time [s] | < 0.3 | ||||||||
Integrated watchdog | yes | ||||||||
Inputs / outputs | |||||||||
Number of inputs and outputs | Number of digital outputs: 2 | ||||||||
Outputs |
|||||||||
Total number of outputs | 2 | ||||||||
Output signal | switching signal; IO-Link; (configurable) | ||||||||
Electrical design | PNP/NPN | ||||||||
Number of digital outputs | 2 | ||||||||
Output function | normally open / normally closed; (parameterisable) | ||||||||
Max. voltage drop switching output DC [V] | 2.5 | ||||||||
Permanent current rating of switching output DC [mA] | 150; (200 (…60 °C) 250 (…40 °C)) | ||||||||
Switching frequency DC [Hz] | < 170 | ||||||||
Short-circuit protection | yes | ||||||||
Type of short-circuit protection | pulsed | ||||||||
Overload protection | yes | ||||||||
Measuring/setting range PN7070 | |||||||||
Measuring range |
|
||||||||
Factory setting / CMPT = 2 |
|||||||||
Set point SP |
|
||||||||
Reset point rP |
|
||||||||
Min. difference between SP and rP |
|
||||||||
In steps of |
|
||||||||
Status_B High Resolution / CMPT = 3 | |||||||||
Set point SP |
|
||||||||
Reset point rP |
|
||||||||
Min. difference between SP and rP |
|
||||||||
In steps of |
|
||||||||
Accuracy / deviations | |||||||||
Switch point accuracy [% of the span] | < ± 0,5 | ||||||||
Repeatability [% of the span] | < ± 0,1; (with temperature fluctuations < 10 K) | ||||||||
Characteristics deviation [% of the span] | < ± 0,25 (BFSL) / < ± 0,5 (LS); (BFSL = Best Fit Straight Line; LS = limit value setting) | ||||||||
Hysteresis deviation [% of the span] | < ± 0,25 | ||||||||
Long-term stability [% of the span] | < ± 0,05; (per 6 months) | ||||||||
Temperature coefficient zero point [% of the span / 10 K] | 0,2; (-25…80 °C) | ||||||||
Temperature coefficient span [% of the span / 10 K] | 0,2; (-25…80 °C) | ||||||||
Response times | |||||||||
Response time [ms] | < 3 | ||||||||
Delay time programmable dS, dr [s] | 0…50 | ||||||||
Software / programming | |||||||||
Parameter setting options | hysteresis / window; normally open / normally closed; switching logic; switch-on/switch-off delay; Damping; Display unit | ||||||||
Interfaces | |||||||||
Communication interface | IO-Link | ||||||||
Transmission type | COM2 (38,4 kBaud) | ||||||||
IO-Link revision | 1.1 | ||||||||
SDCI standard | IEC 61131-9 | ||||||||
SIO mode | yes | ||||||||
Required master port type | A; (when pin 2 not connected: B) | ||||||||
Process data analogue | 1 | ||||||||
Process data binary | 2 | ||||||||
Supported DeviceIDs |
|
||||||||
Note |
|
||||||||
Factory setting / CMPT = 2 | |||||||||
Profiles | Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis | ||||||||
Min. process cycle time [ms] | 2.3 | ||||||||
IO-Link resolution pressure [bar] | 1 | ||||||||
IO-Link resolution pressure [MPa] | 0.1 | ||||||||
IO-Link process data (cyclical) |
|
||||||||
IO-Link functions (acyclical) | application specific tag | ||||||||
Status_B High Resolution / CMPT = 3 | |||||||||
Profiles | Smart Sensor ED2: Digital Measuring Sensor (0x000A), Identification and Diagnosis (0x4000) | ||||||||
Min. process cycle time [ms] | 3 | ||||||||
IO-Link resolution pressure [bar] | 0.2 | ||||||||
IO-Link resolution pressure [MPa] | 0.02 | ||||||||
IO-Link process data (cyclical) |
|
||||||||
IO-Link functions (acyclical) | application specific tag | ||||||||
Operating conditions |
|||||||||
Ambient temperature [°C] | -25…80 | ||||||||
Storage temperature [°C] | -40…100 | ||||||||
Protection | IP 65; IP 67 | ||||||||
Tests / approvals | |||||||||
EMC |
|
||||||||
Shock resistance |
|
||||||||
Vibration resistance |
|
||||||||
MTTF [years] | 214 | ||||||||
UL approval |
|
||||||||
Pressure Equipment Directive | Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request | ||||||||
Mechanical data | |||||||||
Weight [g] | 231 | ||||||||
Materials | 1.4542 (17-4 PH / 630); stainless steel (1.4404 / 316L); PBT+PC-GF30; PBT-GF20; PC | ||||||||
Materials (wetted parts) | 1.4542 (17-4 PH / 630) | ||||||||
Min. pressure cycles | 100 million | ||||||||
Tightening torque [Nm] | 25…35; (recommended tightening torque; depends on lubrication, seal and pressure rating) | ||||||||
Process connection | threaded connection G 1/4 internal thread | ||||||||
Restrictor element integrated | no (can be retrofitted) | ||||||||
Displays / operating elements | |||||||||
Display |
|
||||||||
Remarks | |||||||||
Pack quantity | 1 pcs. | ||||||||
Electrical connection | |||||||||
Connection | Connector: 1 x M12; Contacts: gold-plated |