PT5400
Pressure transmitter PT5400
Product characteristics | |||||
---|---|---|---|---|---|
Output signal | analogue signal | ||||
Measuring range |
|
||||
Process connection | threaded connection G 1/4 external thread (DIN EN ISO 1179-2) | ||||
Application | |||||
Application | for industrial applications | ||||
Media | liquids and gases | ||||
Medium temperature [°C] | -40…90 | ||||
Min. bursting pressure |
|
||||
Pressure rating |
|
||||
Note on pressure rating |
|
||||
Vacuum resistance [mbar] | -1000 | ||||
Type of pressure | relative pressure | ||||
Electrical data | |||||
Operating voltage [V] | 8.5…36 DC | ||||
Min. insulation resistance [MΩ] | 100; (500 V DC) | ||||
Protection class | III | ||||
Reverse polarity protection | yes | ||||
Power-on delay time [s] | < 0.1 | ||||
Inputs / outputs | |||||
Number of inputs and outputs | Number of analogue outputs: 1 | ||||
Outputs | |||||
Total number of outputs | 1 | ||||
Output signal | analogue signal | ||||
Number of analogue outputs | 1 | ||||
Analogue current output [mA] | 4…20 | ||||
Max. load [Ω] | (Ub – 8,5 V) / 21,5 mA; @8,5V= 0 Ω; @12V max. 160 Ω; @24V max. 720 Ω | ||||
Short-circuit proof | yes | ||||
Overload protection | yes | ||||
Measuring/setting range | |||||
Measuring range |
|
||||
Accuracy / deviations | |||||
Repeatability [% of the span] | < ± 0,05; (with temperature fluctuations < 10 K) | ||||
Characteristics deviation [% of the span] | < ± 0,5; (incl. drift when overtightened, zero point and span error, non-linearity, hysteresis) | ||||
Linearity deviation [% of the span] | < ± 0,1 (BFSL) / < ± 0,2 (LS) | ||||
Hysteresis deviation [% of the span] | < ± 0,2 | ||||
Long-term stability [% of the span] | < ± 0,1; (per 6 months) | ||||
Temperature coefficient zero point and span [% of the span / 10 K] | < 0,1 (-25…90 °C) / < 0,2 (-40…-25 °C) | ||||
Response times | |||||
Step response time analogue output [ms] | 1 | ||||
Operating conditions | |||||
Ambient temperature [°C] | -40…90 | ||||
Storage temperature [°C] | -40…100 | ||||
Protection | IP 67; IP 69K | ||||
Tests / approvals | |||||
EMC |
|
||||
Shock resistance |
|
||||
Vibration resistance |
|
||||
MTTF [years] | 686 | ||||
Pressure Equipment Directive | Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request | ||||
Mechanical data | |||||
Weight [g] | 60 | ||||
Materials | 1.4542 (17-4 PH / 630); stainless steel (1.4404 / 316L); PEI | ||||
Materials (wetted parts) | 1.4542 (17-4 PH / 630) | ||||
Min. pressure cycles | 60 million; (at 1.2 times nominal pressure) | ||||
Tightening torque [Nm] | 25…35; (recommended tightening torque; depends on lubrication, seal and pressure rating) | ||||
Process connection | threaded connection G 1/4 external thread (DIN EN ISO 1179-2) | ||||
Process connection sealing | FKM (DIN EN ISO 1179-2) | ||||
Restrictor element integrated | no (can be retrofitted) | ||||
Remarks | |||||
Remarks |
|
||||
Pack quantity | 1 pcs. | ||||
Electrical connection | |||||
Connection | Connector: 1 x M12 |