PY9920
Pressure sensor with display PY9920
Product characteristics | |||||||||
---|---|---|---|---|---|---|---|---|---|
Output signal | switching signal | ||||||||
Measuring range |
|
||||||||
Process connection | threaded connection G 1/4 internal thread | ||||||||
Application |
|||||||||
Medium temperature [°C] | -25…80 | ||||||||
Min. bursting pressure |
|
||||||||
Pressure rating |
|
||||||||
Electrical data | |||||||||
Operating voltage tolerance [%] | 5…10 | ||||||||
Operating voltage [V] | 85…265 AC | ||||||||
Nominal voltage AC [V] | < 250 | ||||||||
Current consumption [mA] | < 10 | ||||||||
Min. insulation resistance [MΩ] | 100; (500 V DC) | ||||||||
Protection class | II | ||||||||
Reverse polarity protection | no | ||||||||
Power-on delay time [s] | 0.2 | ||||||||
Integrated watchdog | yes | ||||||||
Inputs / outputs | |||||||||
Number of inputs and outputs | Number of digital outputs: 1 | ||||||||
Outputs | |||||||||
Total number of outputs | 1 | ||||||||
Output signal | switching signal | ||||||||
Electrical design | Triac | ||||||||
Number of digital outputs | 1 | ||||||||
Output function | normally open / normally closed; (parameterisable) | ||||||||
Max. voltage drop switching output AC [V] | 2 | ||||||||
Permanent current rating of switching output AC [mA] | 250; ((…70 °C) 1000 (…60 °C) 1500 (…45 °C) 2500 (…20 °C)) | ||||||||
Switching frequency AC [Hz] | < 160 | ||||||||
Short-circuit proof | no | ||||||||
Overload protection | no | ||||||||
Measuring/setting range | |||||||||
Measuring range |
|
||||||||
Set point SP |
|
||||||||
Reset point rP |
|
||||||||
In steps of |
|
||||||||
Accuracy / deviations |
|||||||||
Switch point accuracy [% of the span] | < ± 1,0 | ||||||||
Repeatability [% of the span] | < ± 0,1; (with temperature fluctuations < 10 K) | ||||||||
Linearity deviation [% of the span] | < ± 0,5 | ||||||||
Hysteresis deviation [% of the span] | < ± 0,1 | ||||||||
Long-term stability [% of the span] | < ± 0,1; (per year) | ||||||||
Temperature coefficient zero point [% of the span / 10 K] | < ± 0,2; (-25…80 °C) | ||||||||
Temperature coefficient span [% of the span / 10 K] | < ± 0,3; (-25…80 °C) | ||||||||
Response times | |||||||||
Delay time programmable dS, dr [s] | 0, 0,2,…10, 11,…50 | ||||||||
Damping for the switching output dAP [s] | 0…4 | ||||||||
Software / programming | |||||||||
Adjustment of the switch point | programming button | ||||||||
Parameter setting options | hysteresis / window; normally open / normally closed; switch-on/switch-off delay; Damping; adaptation of displayed values; display can be rotated and switched off; Display unit | ||||||||
Operating conditions | |||||||||
Ambient temperature [°C] | -25…80 | ||||||||
Storage temperature [°C] | -40…100 | ||||||||
Protection | IP 67 | ||||||||
Tests / approvals | |||||||||
EMC |
|
||||||||
Shock resistance |
|
||||||||
Vibration resistance |
|
||||||||
MTTF [years] | 224.58 | ||||||||
Pressure Equipment Directive | Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request | ||||||||
Mechanical data |
|||||||||
Weight [g] | 387 | ||||||||
Materials | FKM; PA; PBT; PC; stainless steel (1.4301 / 304) | ||||||||
Materials (wetted parts) | stainless steel (1.4305 / 303); ceramics; FKM | ||||||||
Min. pressure cycles | 100 million | ||||||||
Process connection | threaded connection G 1/4 internal thread | ||||||||
Restrictor element integrated | yes | ||||||||
Displays / operating elements | |||||||||
Display |
|
||||||||
Display unit | bar; psi; MPa | ||||||||
Electrical connection | |||||||||
Required protection | miniature fuse to IEC60127-2 sheet 1; ≤ 5 A; fast acting | ||||||||
Remarks | |||||||||
Remarks |
|
||||||||
Pack quantity | 1 pcs. | ||||||||
Electrical connection | |||||||||
Connection | Connector: 1 x 1/2″ |