– High precision control
– Various alarm functions
– Detachable, expandable structure
– Temperature, humidity independent PID control
– Built-in communication function (RS485)
– Digital Recorder function (internal memory, SD card storage)
– Contact input (DI) with up to 32 contacts, contact output (DO) with up to 32 contacts
– Color TFT LCD screen with touch panel (640 * 480 resolution)
Suffix code
Model | Code | Description | |||
TH510– | Programmable temperature/Humidity controller | ||||
Display | 1 | Display(5.7″ TFT LCD) | |||
N | None | ||||
Input/output | 1 | 8 input points/6 output points(1 module)+Power module+Control module | |||
2 | 8 input points/14 output points(2 modules)+Power module+Control module | ||||
3 | 16 input points/16 output points(3 modules)+Power module+Control module | ||||
N | No input/output | ||||
Language | S | Korean, English, and Chinese(Simplified) |
※ This product consists of the display and control(power, control, input, and output modules) |
(Up to 32 contact input/output points, respectively) |
[Components] |
Product | Model | Description |
Display | TH510-1N | Display(5.7″ TFT LCD) |
Control module | TH510-MAIN | Temperature•Humidity control module |
Power module | TM-PWR | Power module |
Input module | TM-DI | Module with 16 input points |
Output module | TM-DO | Module with 8 output points |
Input/output module | TM-DIO | Module with 8 input and 6 output points |
· Specification
[input] |
Input type | 2 types of thermoresistor (Pt-100, KPt-100), 2 types of DC voltage (1 – 5 V, 0 – 30 V) |
Sampling cycle | 250 ㎳ |
Measured current of thermoresistor(RTD) | Approx. 0.21 mA |
Input resistance | Input resistance |
Allowable wire resistance | RTD : Max. 10Ω/wire, DC voltage : 2 ㏀ or less |
Influence of wire resistance | RTD±0.3 ℃/10 Ω (3 wires must have the same wire resistance) |
Allowable input voltage | DC voltage : ±33 V DC or less |
Detection of sensor disconnection(Burn-out) | UP-Scale for disconnection |
[Performance] |
Marking accuracy | Temperature(℃) : ±0.1% ±1 digit of Full Scale, humidity : ±1% ±1 digit of Full Scale | |||||
Insulation resistance | 20 ㏁ or 500 V DC between power and FG terminals | |||||
internal pressure |
|
[General Specifications] |
Power voltage | 100 – 240 V a.c. | ||
Voltage fluctuation rate | ± 10% of supply voltage | ||
Power Consumption | 25 VA (Based on TH510-13) | ||
Ambient temperature | 0 ~ 50 ℃ | ||
Ambient humidity | 20 ~ 90 % RH (However, no condensation) | ||
Ambient temperature | -25℃ ~ 70℃ | ||
Internal vibration | 10 – 55 Hz, Amplitude 0.75 mm, 4 directions in 3 directions, 5 minutes / cycle | ||
Internal shock | 147 m/s², 3 times in 3 directions | ||
Dimensions |
|
||
Weight | 1.79 Kg (Based on TH510-13) |
[Control function] |
Input | Input calibration(Sensor bias) | 1 Temperature contact : EUS(0~100 %) 1 Humidity contact : EUS(0 ~ 100 %) |
Dry/wet-bulb sensor compensation | Compensate the dry/wet sensor difference after removing the gauze of the wet-bulb sensor. | |
Scaling | DC voltage(VDC) : Input scaling according to conversion range | |
Input filter(LPF) | 0 ~ 120 sec | |
Control mode | Operation type | Constant-value / Program control |
Control output | Temperature control output | SSR output or SCR (4 – 20 mA DC) output |
Humidity control output | ||
Control operation | Pattern | 100 patterns(1 pattern/100 segments) |
Segment | 2000 segments | |
Group | 16 groups(temperature 4 zones X humidity 4 zones) | |
Auto tuning | 16 groups(temperature 4 zones X humidity 4 zones) | |
Proportional band | 0.00 ~ 100.00 % (For 0.00 %, ON/OFF control) | |
Integral time | 0.0 ~ 3,000 sec (OFF when 0 sec) | |
Derivative time | ||
ON/OFF control | Set 0.0 to proportional band(PB) | |
Normal Open/Normal Close | According to selection of Normal Open/Normal Close for control output | |
Hysteresis | EUS (0 ~ 100 %) | |
Transmission output | Temperature, Humidity | Current output(4 – 20 ㎃ d.c.) Select between indication value (PV), set value (SV), and output amount (MV) |
Scaling | Auto scaling for defined upper/lower limit range (4 – 20 mA DC) | |
Alarm setting | Alarm setting | System alarm : 8 points Assign 4 of 8 pattern alarms to a pattern |
Alarm type | Absolute high/low limit, deviation high/low limit, in range/out of range (alarm direction, hold) | |
Absolute alarm setting range | EU (0 ~ 100 %) | |
Offset information setting range | EUS (-100 ~ 100 %) | |
Hysteresis | EUS (0 ~ 100 %) | |
Memory specifications | Internal memory | Nonvolatile flash memory (80 MB) |
External memory | SD card(2 GB) : Saving of 1 year at 1 S interval | |
Saving interval | 1 ~ 360 | |
Memory information | Program information, setting value, recovery, and temperature setting/specific/output value |
[Display specifications] |
Display | TFT color LCD (115.2 × 86.4 mm) |
Number of Pixels | 640 X 480 Pixel |
Back light | LED Back light |
Life cycle of back light | Approx. 40,000 h |
Touch type | Resistive type (4 Wires) |
Language | Korean/English/Chinese(Simplified) |
[Output specifications] |
Contact output(DO) | Up to 32 relay | A Contact | 30 V d.c. 3 A max, 250 V a.c. 3 A |
B Contact | NO : 30 V d.c. 5 A max. 250 V a.c. 5 A NC : 30 V d.c. 1 A max. 250 V a.c. 5 A |
||
Control output | SSR output | ON : 18 V DC Pulse voltage(800 Ω or more load resistance) | |
SCR output | 4 – 20 mA DC (600 Ω or less load resistance) | ||
Transmission output | Current output | 4 – 20 ㎃ d.c | |
Load resistance | 600 Ω or less load resistance | ||
Output limit | -5.00 ~ 105.00 % | ||
Output type | Specific value(PV), Setting value(SV), Output(MV), and random | ||
Refresh interval | 250 ㎳ |
[Contact input] |
Input score | Up to 32 points |
Input signal | Non-voltage contact input |
Operating condition | Running / Always |
[Communication specifications] |
Applied standard | RS485 |
Max. connection number | 1:32 (address 1 ~ 99) |
Communication type | 2-wire |
Synchronization | Asynchronous |
Communication distance | Approx. 1.2 km or less |
Communication speed | 9600, 19200, 38400, 57600, 115200 bps |
Data Length | 7/8 Bits |
Parity Bit | NONE / EVEN / ODD |
Stop Bit | 1 / 2 Bit(s) |
Protocol | PC-Link / PC-link + SUM / MODBUS ASC / MODBUS RTU |
Response Time | 0 ~ 100 ㎳ |
[Range configuration by input type ] |
Input type | Temperature | Humidity | ||||
Measuring range (℃) | accuracy | Measuring range (%RH) |
accuracy | |||
Thermoresistor (RTD) | Pt100 Ω | Pt-1 | -100.0 ~ 300.0 | ±0.1 % of FS ±1 Digit |
0.0 ~ 100.0 | ±1 % of FS ±1 Digit |
Pt-2 | -100.00 ~ 150.00 | |||||
KPt100 Ω | KPt-1 | -100.0 ~ 300.0 | ||||
KPt-2 | -100.00 ~ 150.00 | |||||
DC voltage (VDC) | 1 – 5 V | -100.0 ~ 300.0 | ±0.1 % of FS ±1 Digit |
|||
0 – 30 V | -100.0 ~ 300.0 |